HGM-MZ:
CFC: R11, R12, R113, R114, R502, HFP
HFC:
R125, R-134a, R236FA, R245Fa, R32, R-404a (HP62), R-407a, R-407c (AC9000), R-407F, R-410a (AZ20), R422a, R422d, R427a, R-507 (AZ50), R-508b (SUVA95)
HCFC:
R21, R22, R23, R123, R124, R227, R500, R503, R401A (MP39),
R402A (HP80), R402 (HP81), R408A, R409A, R236FA, R125, R245FA, R422A, R422D, R427A
Halon:
H1211, H1301, H2402
Other:
FA188, FC72, H1234YF, H1234ZE, N1230, N7100, N7200, N7300, N7600, R424A, R426A, R438A, CUSTOM
Measurement Range: All gases 0 to 10,000 ppm
AGM-MZ:
Gas:
Ammonia (NH3) / R-717
Measurement Range:
0 to 10,000 ppm
CO2-MZ:
Gas:
Carbon Dioxide (CO2) / R-744
Measurement Range:
300 to 10,000 ppm
Sensor:
NDIR, 7 - 10 years
Coverage: 4 point standard, expandable to 16 points in 4 point increments
Front Panel:
3 Indicator lights
Sampling Mode:
Automatic or manual (hold)
Re-Zero:
Auto or on zone change
Response Time:
5 to 315 seconds – depending on air line length and number of zones
Monitoring Distance:
1,200 ft (366 m) maximum for combined length of sample + exhaust tubing (each zone)
Conditioned Signal:
Dual optional 4-20 mA DC isolated outputs.
Alarms:
Four SPDT alarm contacts rated 2A at 250 VAC (inductive) 5 A at 250 VAC (resistive). Three are assigned to PPM level alarms, one assigned to system faults.
Communications:
Full two-way communications with Remote Display Module or Building Management System via RS-485 serial interface. RS-232C communications port standard.
Operating Temp.:
0 to 50°C
Ambient Humidity:
5 to 90%, non condensing
Power Supply:
100 to 240 VAC, 50/60 Hz, 20 W
Dimensions:
31.06 cm x 34.80 cm x 12.60 cm
Weight:
6.8 kg
IMR Environmental Equipment, Inc. reserves the right to adopt technical modifications without prior notice.